Roop's Law Assist
Waitlist

Uttar Pradesh Shasan Atrikt Urja Shrot Vibhag

notifications · 2001 · State unknown

Download PDFParent ActBack to Subordinates
Parent: THE ENERGY CONSERVATION ACT, 2001 (6ed0c10d12a3ffa994bbdf21a0cbc6f587e2d2fa)

Text

Uttar Pradesh Shasan Atrikt Urja Shrot Vibhag In persuance of the provisions of clause (3) of Article 348 of the Constitution the Governor is pleased to order the publication of the following English translation of notification no 1198087&Add Energy Sources Deptt.@2018 Dated July 26 ,2018 NOTIFCATION NO 1198/87&Add.Energy Sources Deptt.@2018 Dated July 26 ,2018 In exercise of the powers conferred by section 15 of the Energy Conservation Act 2001 (Central Act No 52 of 2001)the Governor in consultation with the Bureau of Energy Efficiency is pleased to approve the draft of Energy Conservation Building Code- 2018 and to direct that the notification and the procedure of implementation thereof shall be adopted: The Governor is further pleased to approve that the construction of such government buildings of the State of which designing work has not been completed, which are covered under the perview of Energy Conservation Building Code 2018 shall be caused to be done in accordance with Energy Conservation Building Code 2018 By, Order Alok Kumar Principal Secretary UTTAR PRADESH ENERGY CONSERVATION BUILDING CODE 20 18 2 1. Purpose The purpose of the Uttar Pradesh Energy Conservation Building Code (Code) is to provide minimum requirements for the energy-efficient design and construction of buildings in Uttar Pradesh falling under climatic zone: Composite, using ECBC- 2017. The Code also provides two additional sets of incremental requirements for buildings to achieve enhanced levels of energy efficiency that go beyond the minimum requirements. 3 2. Scope The Code is applicable to buildings o building complexes that meet either of following: (a) has a connected load of 100 kW Or greater; or (b) has a contract demand of 120 kVA o greater; Or C) plot area of the building is more t

Rule TOC

1 · Purpose
2 · Scope The Code is applicable to buildings o building complexes that meet either of following: (a) has a connected load of 100 kW Or greater; or (b) has a contract demand of 120 kVA o greater; Or C) plot area of the building is more than 1000 m? with minimum 2000 m? as built-up area (excluding basement)
2 · 1 Energy Efficiency Performance Levels
2 · 2 Building Systems The provisions of this code apply to:
2 · 3 Precedence
2 · 4 Reference Standards
2 · 5 Building Classification Any one or more building or part of a building with commercial use is classified as per the functional requirements of its design, construction, and use: The key classification is as below: a) Hospitality: Any building in which sleeping accommodation is provided for commercial purposes, except any building classified under Health Care: Buildings and structures under Hospitality shall include the following: I No-star Hotels like Lodging-houses, dormitories, no-star hotels/ motels ii. Resort iii. Star Hotel b) Health Care: Any building or part thereof, which is used for purposes such as medical or other treatment or care of persons suffering from physical or mental illness, disease, or infirmity; care of infants, convalescents, or aged persons, and for penal or correctional detention in which the liberty ofthe inmates is restricted. Health Care buildings ordinarily provide sleeping accommodation for the occupants: Buildings and structures like hospitals, sanatoria, out-patient healthcare, laboratories, research establishments, and test houses are included under this type: c) Assembly: Any building or part of a building, where number of persons congregate or gather for amusement, recreation, social, religious, patriotic, civil, travel and similar purposes Buildings like theatres or motion picture halls, gathering halls, and transport buildings like airports, railway stations, bus stations, and underground and elevated mass rapid transit system are included in this group. d) Business: Any building or part thereof which is used for transaction of business, for keeping of accounts and records and similar purposes, professional establishments, and service facilities. There are two subcategories under Business Daytime Business and 24-
1 · Star Hotel
2 · _ No Star Hotel
3 · Resort
1 · College
2 · University
3 · Institution
4 · School
1 · Hospital
2 · Out-patient Healthcare
1 · Shopping Mall
2 · Stand-alone Retails
1 · Large Office 30,000 m2)
2 · Medium Office (10,00Om2 _ 30,000 m2)
3 · Small Office (< 10,000 m2)
1 · Multiplex
2 · Theatre
3 · Compliance and Approach
3 · 1 General
3 · 1.1 Energy Performance Index The Energy Performance Index (EPI) of a building is its annual energy consumption in kilowatt- hours per square meter of the building: While calculating the EPI of a building, the area of unconditioned basements shall not be included: EPI can be determined by: Annual Energy Consumption (in kWh) EPI Total builtup area (excluding unconditioned basements) To comply with the Code, EPI shall be calculated based on one of the following: a) Prescriptive Method including Building Envelope Trade-off Method (see 53.2.2) b) Whole Building Performance Method (see 83.2.3)
3 · 1.2 Determining EPI Ratio The EPI Ratio of a building is the ratio of the EPI of the Proposed Building to the EPI of the Standard Building: EPI of Proposed Building EPI Ratio EPI of Standard Building where,
55 · 2, 56.2, and 87.2, and minimally complies with prescriptive requirements of 54.3, 55.3 and 56.3 for ECBC Buildings The EPI of the Proposed Building shall be established through any one of the following two methods described in 83.2
3 · 1.2.1 EPI Ratio through Prescriptive Method ECBC Buildings that demonstrate compliance through Prescriptive Method (83.2.2) shall be deemed to have an EPI equal to the Standard Building EPI, and therefore an EPI Ratio of 1. ECBC+ Buildings and SuperECBC Buildings that demonstrate compliance through Prescriptive Method shall be deemed to have an EPI Ratio equal to the EPI Ratios listed in 89.5 under the applicable building type and climate zone.
3 · 1.2.2 EPI Ratio through Whole Building Performance Method The EPI of buildings that demonstrate compliance through Whole Building Performance Method (53.2.3) shall be calculated using the compliance path defined in 83.1.1 and detailed in 59. The EPI Ratio of a building that uses the Whole Building Performance Method to show compliance, should be less than or equal to the EPI Ratio listed in 59.5 for the applicable building type and climate zone:
3 · 1.2.3 EPI Ratio for Core and Shell Buildings EPI for core and shell buildings shall be calculated for the entire building based on the final design of the common areas and the relevant mandatory undertakingls) in the tenant lease agreement for the leased areas, as per 83.1.2.1 or 53.1.2.2.
3 · 1.2.4 EPI Ratio for Mixed-use Development In a mixed-use building, each commercial part of a building must be classified separately, and EPI Ratio shall be calculated separately for each sub-classification, as per 83.1.2.1 or 53.1.2.2. The EPI Ratio of a mixed-use Proposed Building shall be calculated based on area-weighted average method: To calculate the reference maximum design EPI Ratio, listed in Table 9-5 through Table 9-7, applicable for the mixed-use building, each commercial part of mixed-use building shall be classified separately, and, a) If a part of the mixed-use building has different classification and is less than 10% of the total above grade area (AGA), the EPI Ratio of the mixed-use Proposed Building shall be less than or equal to Maximum Allowed EPI listed in Table 9-5 through Table 9-7, for the building sub-classification having highest percentage of above grade floor area.
3 · 2 Compliance Approaches Buildings that fall within the scope of the Code as mentioned in 52, shall comply with the Code by meeting all the mandatory requirements (see 53.2.1) and any of the compliance paths mentioned in 83.2.2, 83.2.2.1, or 83.2.3.
3 · 2.1 Mandatory Requirements Buildings shall comply with all mandatory requirements mentioned under 54.2, 55.2 _ 86.2, and 57.2, irrespective of the compliance path:
3 · 2.2 Prescriptive Method building complies with the Code using the Prescriptive Method if it meets the prescribed minimum (or maximum) values for envelope components (54.3), comfort systems and controls (55.3, 55.4, 85.5), and lighting and controls (86.3), in addition to meeting all the mandatory requirements.
3 · 2.2.1 Building Envelope Trade-off Method Building Envelope Trade-off Method may be used in place of the prescriptive criteria of 54.3.1, 54.3.2 and 84.3.3. A building complies with the Code using the Building Envelope Trade-off Method if the Envelope Performance Factor (EPF) of the Proposed Building is less than or equal to the EPF of the Standard Building, calculated as per 54.3.5, in addition to meeting the prescriptive requirements for comfort systems and controls (55.3,85.4),and lighting and controls (56.3), and all the mandatory requirements (54.2, 55.2, 56.2 and 57.2).
3 · 2.3 Whole Building Performance Method building complies with the Code using the Whole Building Performance (WBP) Method when the estimated annual energy use of the Proposed Design is less than that of the Standard Design, even though it may not comply with the specific provisions of the prescriptive requirements in 54 trough 57. The mandatory requirements of 54 through 57 (84.2, 55.2, 86.2,and 57.2) shall be met when using the WBP Method:
3 · 3 Compliance Requirements
3 · 3.1 New Building Compliance 3.3.1.1 Full building Compliance New buildings with completed fit-outs shall comply with either the provisions of 54 through 57 of this Code or the Whole Building Performance Method of 59.
3 · 3.1.2 Core and Shell building Compliance New core and shell building shall demonstrate compliance with ECBC requirements for the following base building systems in the common areas: a) Building envelope b) Thermal comfort systems and controls (only those installed by developer/ owner) c) Lighting systems and controls (only those installed by developer/ owner) d) Electrical systems (installed by developer/ owner) e) Renewable energy systems
3 · 3.2 Additions to Existing Buildings Where the new connected load demand of the addition plus the existing building exceeds 100 kW or 120 kVA, the additions shall comply with the provisions of 84 through S7. Compliance may be demonstrated in either of the following ways: a) The addition shall comply with the applicable requirements, or b) The addition, together with the entire existing building, shall comply with the requirements of this Code that shall apply to the entire building, as if it were a new building:
3 · 3.3 Alterations to Existing Buildings Where the connected load or contract demand of the existing building exceeds 100 kW or 120 kVA respectively, part of a building and its systems that are being altered shall meet the provisions of 54 through 57 .
3 · 4 Approved Analytical Tools building following the whole building performance approach shall show compliance through a whole building energy simulation software that has been approved by BEE. Compliance to the daylight requirements of 54.2.3, if calculated through software tools, shall be shown through a daylighting software approved by BEE. The list of BEE approved software for whole building energy simulation and daylighting analysis is given in Appendix E.
3 · 5 Administrative Requirements Administrative requirements, including but not limited to, permit requirements, enforcement, interpretations, claims of exemption, approved calculation methods, and rights of appeal are specified by the authority having jurisdiction.
3 · 6 Compliance Documents
3 · 6.1 Compliance Documents Construction drawings and specifications shall show all pertinent data and features of the building, equipment, and systems in sufficient detail to permit the authority having jurisdiction to verify that the building complies with the requirements of this code: Details shall include, but are not limited to:
3 · 6.2 Supplemental Information The authority having jurisdiction may require supplemental information necessary to verify compliance with this code, such as calculations, worksheets, compliance forms, manufacturer's literature, or other data:
4 · Building Envelope 4.1 General The building envelope shall comply with the mandatory provisions of 54.2,and the prescriptive criteria of 54.3.
4 · 2 Mandatory Requirements
4 · 2.1 Fenestration
4 · 2.1.1 U-Factor
4 · 2.1.2 Solar Heat Gain Coefficient SHGC shall be determined for the overall single or multi glazed fenestration product (including the sash and frame) in accordance with ISO-15099 by an accredited independent laboratory, and labeled or certified by the manufacturer.
4 · 2.1.3 Visual Light Transmittance Visual light transmittance (VLT) shall be determined for the fenestration product in accordance with ISO-15099 by an accredited independent laboratory, and labeled or certified by the manufacturer. For unrated products, use the default table in Appendix A_
4 · 2.2 Opaque Construction U-factors shall be calculated for the opaque construction in accordance with ISO-6946. Testing shall be done in accordance with approved ISO Standard for respective insulation type by an accredited independent laboratory, and labeled or certified by the manufacturer. For unrated products, use the default tables in Appendix A
4 · 2.3 Daylighting Above grade floor areas shall meet or exceed the useful daylight illuminance (UDI) area requirements listed in Table 4-1 for 90% of the potential daylight time in a year. Mixed-use buildings shall show compliance as per the criteria prescribed in 82.5. Compliance shall be demonstrated either through daylighting simulation method in 84.2.3.1 or the manual method in 54.2.3.2. Assembly buildings and other buildings where daylighting will interfere with the functions or processes of 50% (or more) of the building floor area, are exempted from meeting the requirements listed in Table 4-1.
4 · 2.3.1 Daylighting Simulation Method Only BEE approved software shall be used to demonstrate compliance through the daylighting simulation method. Buildings shall achieve illuminance level between 100 lux and 2,000 lux for the minimum percentage of floor area prescribed in Table 4-1 for at least 90% of the potential daylit time: Illuminance levels for all spaces enclosed by permanent internal partitions (opaque, translucent, or transparent) with height greater or equal to 2 m from the finished floor, shall be measured as follows:
4 · 2.3.2 Manual Daylighting Compliance Method This method can be used for demonstrating compliance with daylighting requirements without simulation. Daylight extent factors (DEF) mentioned in Table 4-3 shall be used for manually
2 · 5
2 · 0
0 · 7
0 · 5
2 · 8
2 · 2
1 · 1
0 · 7
2 · 4
2 · 0
1 · 3
0 · 6
1 · 7
2 · 2
1 · 5
0 · 8
2 · 8
2 · 3
1 · 5
1 · 1
3 · 0
2 · 5
1 · 8
1 · 5
20 · 4
3 · 0
2 · 5
1 · 8
1 · 6
3 · 5
3 · 0
2 · 1
1 · 8
4 · 2.4 Building Envelope Sealing Following areas of the building envelope, of all except naturally ventilated buildings or spaces, shall be sealed, caulked, gasketed, or weather-stripped: a) Joints around fenestration, skylights, and door frames b) Openings between walls and foundations, and between walls and roof, and wall panels c) Openings at penetrations of utility services through roofs, walls, and floors d) Site-built fenestration and doors e) Building assemblies used as ducts or plenums f) All other openings in the building envelope g) Exhaust fans shall be fitted with a sealing device such a5 a self-closing damper h) Operable fenestration should be constructed to eliminate air leakages from fenestration frame and shutter frame
47 · x 10.5 = 493.5 m2
3 · 5
45 · m
3 · 5x3 = 10.5 m
47x · 9 = 423 m2
3 · 0
45 · m
3 · 0x3-9.0m
2 · 1
25 · m
2 · 1x3-6.3m
0 · m (service zone)
1 · 8
4 · 3 Prescriptive Requirements
4 · 3.1 Roof
0 · 20
0 · 26
4 · 3.1.1 Vegetated and Cool Roof All roofs that are not covered by solar photovoltaic, or solar hot water, or any other renewable energy system, or utilities and services that render it unsuitable for the purpose, shall be either cool roofs or vegetated roofs.
4 · 3.2 Opaque External Wall Opaque above grade external walls shall comply with the maximum assembly U-factors in Table 4-7 through Table 4-9.
0 · 34 0.44 0.44
0 · 63
4 · 3.3 Vertical Fenestration
2 · 20
0 · 25
0 · 50 0.25
0 · 25 < PF > 1.0,and,
4 · 3.3.1 U-factor Exception Vertical fenestration on all unconditioned buildings or unconditioned spaces may have maximum U-factor of 5 W/m?.K provided they comply with all conditions mentioned in Table 4- 14.
0 · 27
0 · 27
2 · 0.40
0 · 27
0 · 27
0 · 0
4 · 3.4 Skylights Skylights shall comply with the maximum U-factor and maximum SHGC requirements of Table 4- 15. Skylight roof ratio (SRR), defined as the ratio of the total skylight area of the roof, measured to the outside of the frame, to the gross exterior roof area, is limited to a maximum of 5 % for ECBC Building, ECBC+ Building, and SuperECBC Building, when using the Prescriptive Method for compliance. Table 4-15: Skylight U-factor and SHGC Requirements (U-factor in W/m?.K) Climate Maximum U-factor Maximum SHGC All climatic zones 4.25 0.35
4 · 3.6 Standard Building EPF Calculation EPF of the Standard Building shall be calculated as follows: a) The Standard Building shall have the same building floor area, gross wall area and gross roof area as the Proposed Building: If the building has both 24-hour and daytime occupancies, the distribution between these shall be the same as the Proposed Design. b) The U-factor of each envelope component shall be equal to the criteria from 54 for each class of construction: c) The SHGC of each window shall be equal to the criteria from 84.3.3.
40 · m
0 · 25
0 · 4
25 · m
0 · 27 0.27 0.27 0.27
14 · 82 x 0.40 x 1,000 = 5,928
14 · 82 x 0.33 x 1000 = 4,890.6
5 · Comfort Systems and Controls
5 · 1 General
5 · 2 Mandatory Requirements
5 · 2.1 Ventilation
5 · 2.1.1 Natural Ventilation Design Requirements Naturally ventilated buildings or spaces in a mixed-mode ventilated buildings shall: a) Comply with guidelines provided for natural ventilation in NBC b) Have minimum BEE 3-star rated ceiling fans, if provided with ceiling fans: c) Have exhaust fans complying with minimum efficiency requirements of fans in 55.3, if provided:
5 · 2.1.2 Mechanical Ventilation Air Quantity Design Requirements Buildings that are ventilated using a mechanical ventilation system or spaces in mixed-mode ventilated buildings that are ventilated with mechanical system, either completely or in conjunction with natural ventilation systems, shall:
5 · 2.1.3 Demand Control Ventilation
5 · 2.2 Minimum Space Conditioning Equipment Efficiencies
5 · 2.2.1 Chillers
2530 · & <1,050 21,050 & <1,580 21,580
5 · 4
6 · 5 6.8
5 · 8
7 · 5 8.1
6 · 3
8 · 4
5 · 8
6 · 2
6 · 5 6.7
8 · 8
6 · 3
7 · 0
6 · 5
8 · 9
9 · 1
5 · 2.2.2 Unitary, Split Packaged Air-Conditioners Unitary air-conditioners shall meet or exceed the efficiency requirements given in Table 5-3 through Table 5-5. Window and split air conditioners shall be certified under BEE's Star Labeling Program. EER shall be as per IS 8148 for all unitary, split, packaged air conditioners greater than 10 kWr.
5 · 2.2.3 Variable Refrigerant Flow
5 · 2.2.4 Air Conditioning and Condensing Units Serving Computer Rooms Air conditioning and condensing units serving computer rooms shall meet or exceed the energy efficiency requirements listed in Table 5-7 .
5 · 2.3 Controls
5 · 2.3.1 Timeclock
5 · 2.3.2 Temperature Controls Mechanical heating and cooling equipment in all buildings shall be installed with controls to manage the temperature inside the conditioned zones. Each floor or a building block shall be installed with at least one control to manage the temperature: These controls should meet the following requirements: a) Where a unit provides both heating and cooling, controls shall be capable of providing temperature dead band of 3.0*C within which the supply of heating and cooling energy to the zone is shut off or reduced to a minimum: b) Where separate heating and cooling equipment serve the same temperature zone, temperature controls shall be interlocked to prevent simultaneous heating and cooling: c) Separate thermostat control shall be installed in each guest room of Resort and Star Hotel, ii. room less than 30 m2 in Business, iii: air-conditioned class room, lecture room, and computer room of Educational, iv_ in-patient and out-patient room of Healthcare
5 · 2.3.3 Occupancy Controls Occupancy controls shall be installed to de-energize or to throttle to minimum the ventilation and/or air conditioning systems when there are no occupants in: a) Each guest room in a Resort and Star Hotel b) Each public toilet in a Star Hotel or Business with built up area more than 20,000 m2
5 · 2.3.4 Fan Controls
5 · 2.3.5 Dampers All air supply and exhaust equipment, having a Variable Frequency Drive (VFD), shall have dampers that automatically close upon:
5 · 2.4 Additional Controls for ECBC+ and SuperECBC Buildings ECBC+ building shall comply with requirements of $ 5.2.4 in addition to complying with requirements of 85.2.3.
5 · 2.4.1 Centralized Demand Shed Controls
5 · 2.4.2 Supply Air Temperature Reset Multi zone mechanical cooling and heating systems in ECBC+ and SuperECBC Buildings shall have controls that automatically reset the supply-air temperature in response to building loads or to outdoor air temperature. Controls shall reset the supply air temperature to at least 25% of the difference between the design supply air temperature and the design room air temperature. Exception to $ 5.2.4.2 ECBCt and SuperECBC Buildings in warm humid climate zone:
5 · 2.4.3 Chilled Water Temperature Reset Chilled water systems with a design capacity exceeding 350 kWr supplying chilled water to comfort conditioning systems in ECBC+ and SuperECBC Buildings shall have controls that automatically reset supply water temperatures by representative building loads (including return water temperature) or by outdoor air temperature.
5 · 2.5.1 Variable Air Volume Fan Control
5 · 2.6 Piping and Ductwork
5 · 2.6.1 Piping Insulation Piping for heating, space conditioning, and service hot water systems shall meet the insulation requirements listed in Table 5-8 through Table 5-10. Insulation exposed to weather shall be protected by aluminum sheet metal, painted canvas, or plastic cover. Cellular foam insulation shall be protected as above, or be painted with water retardant paint:
5 · 2.6.2 Ductwork and Plenum Insulation
5 · 2.7 System Balancing
5 · 2.7.1 General
5 · 2.7.2 Air System Balancing Air systems shall be balanced in a manner to first minimize throttling losses; then, for fans with fan system power greater than 0.75 kW, fan speed shall be adjusted to meet design flow conditions.
5 · 2.7.3 Hydronic System Balancing Hydronic systems shall be proportionately balanced in a manner to first minimize throttling losses; then the pump impeller shall be trimmed or pump speed shall be adjusted to meet design flow conditions.
5 · 2.8 Condensers
5 · 2.8.1 Condenser Locations
5 · 2.9 Service Water Heating
5 · 2.9.1 Solar Water Heating To comply with the Code, Hotels and Hospitals in all climatic zones and all buildings in cold climate zone with a hot water system, shall have solar water heating equipment installed to provide for: a) at least 20% ofthe total hot water design capacity if above grade floor area ofthe building is less than 20,000 m2 b) at least 40% ofthe total hot water design capacity if above grade floor area ofthe building is greater than or equal to 20,000 m2
5 · 2.9.2 Heating Equipment Efficiency Service water heating equipment shall meet or exceed the performance and minimum efficiency requirements presented in available Indian Standards
5 · 2.9.3 Other Water Heating System Supplementary heating system shall be designed to maximize the energy efficiency ofthe system and shall incorporate the following design features in cascade: a) Maximum heat recovery from hot discharge system like condensers of air conditioning units,
5 · 2.9.4 Piping Insulation Piping insulation shall comply with $ 5.2.6.1. The entire hot water system including the storage tanks, pipelines shall be insulated conforming to the relevant IS standards on materials and applications.
5 · 2.9.5 Heat Traps Vertical pipe risers serving storage water heaters and storage tanks not having integral heat traps and serving a non-recirculating system shall have heat traps on both the inlet and outlet piping:
5 · 2.9.6 Swimming Pools AIl heated pools shall be provided with a vapor retardant pool cover on or at the water surface. Pools heated to more than 32'C shall have a pool cover with a minimum insulation value of R- 4.1.
5 · 3 Prescriptive Requirements Compliance shall be demonstrated with the prescriptive requirements in this section. Supply, exhaust, and return or relief fans with motor power exceeding 0.37 kW shall meet or exceed the minimum energy efficiency requirements specified in Table 5-12 through Table 5-14 except the following need not comply with the requirement a) Fans in un-ducted air conditioning unit where fan efficiency has already been taken in account to calculate the efficiency standard of the comfort system: b) Fans in Health Care buildings having HEPA filters. c) Fans inbuilt in energy recovery systems that pre-conditions the outdoor air.
5 · 3.1 Pumps Chilled and condenser water pumps shall meet or exceed the minimum energy efficiency requirements specified in Table 5-15 through Table 5-17. Requirements for pumps in district chiller systems and hot water pumps for space heating are limited to the installed efficiency requirement of individual pump equipment only: To show compliance, calculate the total installed pump capacity in kilo watt and achieve the prescribed limits per kilo watt ofrefrigeration installed in the building:
5 · 3.2 Cooling Towers Cooling towers shall meet or exceed the minimum efficiency requirements specified in Table 5 - 18. ECBC+ and SuperECBC Buildings shall have additional VFD installed in the cooling towers.
5 · 3.3 Economizers
5 · 3.3.1 Economizer for ECBC, ECBC+, and SuperECBC Building Each cooling fan system in buildings with built up area greater than 20,000 m?, shall include at least one of the following: a) An air economizer capable of modulating outside-air and return-air dampers to supply 50% of the design supply air quantity as outside-air. b) A water economizer capable of providing 50% of the expected system cooling load at outside air temperatures of 10'C dry-bulb/7.2'C wet-bulb and below:
5 · 3.3.2 Partial Cooling Where required by 55.3.3.1 economizers shall be capable of providing partial cooling even when additional mechanical cooling is required to meet the cooling load.
5 · 3.3.3 Economizer Controls
5 · 3.3.4 Testing Air-side economizers shall be tested in the field following the requirements in 512 Appendix C to ensure proper operation Exception to 55.3.3.4: Air economizers installed by the HVAC system equipment manufacturer and certified to the building department as being factory calibrated and tested per the procedures in 512.
5 · 3.4 Variable Flow Hydronic Systems
5 · 3.4.1 Variable Fluid Flow
5 · 3.4.2 Isolation Valves
5 · 3.4.3 Variable Speed Drives
5 · 3.5 Boilers
5 · 3.6 Energy Recovery AII Hospitality and Healthcare, with systems of capacity greater than 2,100 liters per second and minimum outdoor air supply of 70% shall have air-to-air heat recovery equipment with minimum 50 % recovery effectiveness At least 50 % of heat shall be recovered from diesel and gas fired generator sets installed in Hospitality, Healthcare, and Business buildings with built up area greater than 20,000 m2.
5 · 4 Total System Efficiency Alternate Compliance Approach Buildings may show compliance by optimizing the total system efficiency for the plant side comfort system instead of the individual equipment mentioned under the prescriptive requirement: This alternate compliance approach is applicable for central chilled water plant side system in all building types. The total installed capacity per kilo-watt refrigeration load shall be less than or equal to maximum threshold requirements as specified in Table 5-21. Equipment that can be included in central chilled water plant side system for this alternate approach are chillers, chilled water pumps, condenser water pumps, and cooling tower fan: Compliance check will be based on annual hourly simulation:
5 · 5 Low-energy Comfort Systems Alternative HVAC systems which have low energy use may be installed in place of (or in conjunction with) refrigerant-based cooling systems. Such systems shall be deemed to meet the minimum space conditioning equipment efficiency levels of 55.2.2, but shall comply with all other applicable mandatory provisions of 55.2 as applicable: The approved list of low energy comfort systems1 is given below:
6 · Lighting and Controls
6 · 1 General
6 · 2 Mandatory Requirements
6 · 2.1 Lighting Control
6 · 2.1.1 Automatic Lighting Shutoff a) 90% of interior lighting fittings in building or space of building larger than 300 m? shall be equipped with automatic control device. b) Additionally, occupancy sensors shall be provided in I AIl building types greater than 20,000 m2 BUA, in a AIl habitable spaces less than 30 m?, enclosed by walls or ceiling height partitions. b_ All storage or utility spaces more than 15 m2 in all building types with BUA greater than 20,000 m2. C Public toilets more than 25 m2, controlling at least 80 % of lighting fitted in the toilet_ The lighting fixtures, not controlled by automatic lighting shutoff, shall be uniformly spread in the area. ii. In corridors of all Hospitality greater than 20,000 m2 BUA, controlling minimum 70% and maximum 80% of lighting fitted in the public corridor. The lighting fixtures, not controlled by automatic lighting shut off, shall be uniformly spread in the area. iii . In all Business and all conference or meeting rooms: c) Automatic control device shall function on either: i A scheduled basis at specific programmed times. An independent program schedule shall be provided for areas of no more than 2,500 m2 and not more than one floor, Or, ii. Occupancy sensors that shall turn off the lighting fixtures within 15 minutes of an occupant leaving the space: Light fixtures controlled by occupancy sensors shall have
6 · 2.1.2 Space Control Each space enclosed by ceiling-height partitions shall have at least one control device to independently control the general lighting within the space: Each control device shall be activated either manually by an occupant or automatically by sensing an occupant: Each control device shall
6 · 2.1.3 Control in Daylight Areas a) Luminaires, installed within day lighting extent from the window as calculated in $ 4.2.3, shall be equipped with either a manual control device to shut off luminaires, installed within day lit area, during potential daylit time of a day or automatic control device that: i Has a delay of minimum 5 minutes, or, ii. Can dim or step down to 50% of total power. b) Overrides to the daylight controls shall not be allowed: c) For SuperECBC Buildings, Lighting Power Density adjustment factor of 20% shall be allowed to all spaces with more than 70% of their area under daylight controls.
6 · 2.1.4 Centralized Controls for ECBC+ and SuperECBC Buildings ECBC+ and SuperECBC building shall have centralized control system for schedule based automatic lighting shutoff switches:
6 · 2.1.5 Exterior Lighting Control a) Lighting for all exterior applications not exempted in 56.3.5 shall be controlled by a photo sensor or astronomical time switch that is capable of automatically turning off the exterior lighting when daylight is available or the lighting is not required: b) Lighting for all exterior applications, of Schools and Business with built up area greater than 20,000 m2, shall have lamp efficacy not less than 80 lumens per watt; 90 lumens per
6 · 2.1.6 Additional Control
6 · 2.2 Exit Signs Internally-illuminated exit signs shall not exceed 5 Watts per face.
6 · 3 Prescriptive Requirements
6 · 3.1 Interior Lighting Power The installed interior lighting power for a building or a separately metered or permitted portion of a building shall be calculated in accordance with 56.3.4 and shall not exceed the interior lighting power allowance determined in accordance with either 86.3.2 or 56.3.3. Tradeoffs of interior lighting power allowance among portions of the building for which a different method of calculation has been used are not permitted: Exception to 56.3: The following lighting equipment and applications shall not be considered when determining the interior lighting power allowance, nor shall the wattage for such lighting be included in the installed interior lighting power. However, any such lighting shall not be
6 · 3.2 Building Area Method Determination of interior lighting power allowance (watts) by the building area method shall be in accordance with the following: Determine the allowed lighting power density for each appropriate building area type from Table 6-1 for ECBC Buildings, from Table 6-2 for ECBCt Buildings and from Table 6-3 for SuperECBC Buildings. a) Calculate the gross lighted carpet area for each building area type: b) The interior lighting power allowance is the sum of the products of the gross lighted floor area of each building area times the allowed lighting power density for that building area type.
6 · 3.3 Space Function Method Determination of interior lighting power allowance (watts) by the space function method shall be in accordance with the following: a) Determine the appropriate building type and the allowed lighting power density from Table 6-4 for ECBC Buildings, Table 6-5 for ECBC+ Buildings and, Table 6-6 for SuperECBC Buildings. In cases where both a common space type and building specific space type are listed, building specific space type LPD shall apply: b) For each space, enclosed by partitions 80% or greater than ceiling height, determine the gross carpet area by measuring to the face of the partition wall: Include the area of balconies or other projections. Retail spaces do not have to comply with the 80% partition height requirements. c) The interior lighting power allowance is the sum of the lighting power allowances for all spaces. The lighting power allowance for a space is the product ofthe gross lighted carpet area of the space times the allowed lighting power density for that space:
2 · 20
3 · 00
17 · 1
10 · 0
6 · 80
8 · 60 5.50
7 · 50 8.00
13 · 7
5 · 70
9 · 10
10 · 9 9.10
7 · 70
10 · 9 12.1 14.1
9 · 10
18 · 3
10 · 0
22 · 6
21 · 5
6 · 40
16 · 4 18.8
3 · 60
5 · 10
7 · 85 11.3
13 · 1 12.9
11 · 0
11 · 3
10 · 8
3 · 20
8 · 20 6.50
10 · 0
10 · 0
11 · 5
7 · 1
7 · 7
7 · 1
887 · 5
7 · 1
5 · 5
18 · 3
10 · 0
7 · 7
7 · 1
6 · 8
12 · 1
6 · 3.4 Installed Interior Lighting Power The installed interior lighting power calculated for compliance with 86.3 shall include all power used by the luminaires, including lamps, ballasts, current regulators, and control devices except as specifically exempted in 56.1. Exception to 56.3.4: If two or more independently operating lighting systems in a space are controlled to prevent simultaneous user operation, the installed interior lighting power shall be based solely on the lighting system with the highest power:
6 · 3.4.1 Luminaire Wattage Luminaire efficacy shall be 0.7 or above. Luminaire wattage incorporated into the installed interior lighting power shall be determined in accordance with the following: a) The wattage of incandescent luminaires with medium base sockets and not containing permanently installed ballasts shall be the maximum labeled wattage of the luminaires: b) The wattage of luminaires containing permanently installed ballasts shall be the operating input wattage of the specified lamp/ballast combination. Operating input wattage can be either values from manufacturers' catalogs or values from independent testing laboratory reports.
6 · 3.5 Exterior Lighting Power Connected lighting power of exterior lighting applications shall not exceed the lighting power limits specified in Table 6-7 for ECBC Buildings, Table 6-8 for ECBC+ Buildings and Table 6-9 for SuperECBC Buildings Trade-offs between applications are not permitted.
10 · W/m? of canopied area
90 · W / linear m of door width
60 · W/lin m of door width
5 · 0 W/m? of vertical facade area
1 · 6 W/m?
2 · 0 W/m2
10 · 0 W/m2
0 · 5 W/m?
9 · 0 W/m2
8 · 0 W/m? of canopied area
72 · W/ linear m of door width
48 · W/lin m of door width
4 · 0 W/m? of vertical facade area
1 · 3 W/m?
1 · 6 W/m?
8 · 0 W/m?
0 · 4 W/m?
7 · 2 W/m?
5 · 0 W/m? of canopied area
45 · W/ linear m of door width
30 · W/lin m of door width
2 · 5 W/m? of vertical facade area
0 · 8 W/m2
1 · 0 W/m?
5 · 0 W/m?
0 · 25 W/m?
4 · 5 W/m?
7 · Electrical and Renewable Energy Systems
7 · 1 General
7 · 2 Mandatory Requirements
7 · 2.1 Transformers
7 · 2.1.1 Maximum Allowable Power Transformer Losses
50 · % Load 100% Load 50 % Load 100% Load 50 % Load 100% Load
4 · 5
4 · 5
4 · 5
4 · 5
4 · 5
4 · 5
4 · 5
4 · 5
4 · 5
4 · 5
4 · 5
6 · 25
6 · 25
6 · 25
4 · 5
4 · 5
4 · 5
4 · 5
4 · 5
4 · 5
4 · 5
4 · 5
4 · 5
4 · 5
4 · 5
6 · 25
6 · 25
6 · 25
7 · 2.1.2 Measurement and Reporting of Transformer Losses
7 · 2.1.3 Voltage Drop Voltage drop for feeders shall not exceed 2% at design load: Voltage drop for branch circuit shall not exceed 3% at design load:
7 · 2.2 Energy Efficient Motors Motors shall comply with the following: a) Three phase induction motors shall conform to Indian Standard (IS) 12615 and shall fulfil the following efficiency requirements: ECBC Buildings shall have motors of IE 2 (high efficiency) class or a higher class ii. ECBC+ Buildings shall have IE 3 (premium efficiency) class motors or higher class ii. SuperECBC Buildings shall have IE 4 (super premium efficiency) class motors
7 · 2.3 Diesel Generator (DG) Sets BEE star rated DG sets shall be used in all compliant buildings DG sets in buildings greater than 20,000 m2 BUA shall have: a) minimum 3 stars rating in ECBC Buildings b) minimum 4 stars rating in ECBC+ Buildings c) minimum 5 stars rating in SuperECBC Buildings
7 · 2.4 Check-Metering and Monitoring a) Services exceeding 1000 kVA shall have permanently installed electrical metering to record demand (kVA) energy (kWh), and total power factor. The metering shall also display current (in each phase and the neutral), voltage (between phases and between each phase and neutral), and total harmonic distortion (THD) as a percentage of total current: b) Services not exceeding 1000 kVA but over 65 kVA shall have permanently installed electric metering to record demand (kW), energy (kWh), and total power factor (or kVARh):
7 · 2.5 Power Factor Correction
7 · 2.6 Power Distribution Systems The power cabling shall be sized so that the distribution losses do not exceed a) 3% of the total power usage in ECBC Buildings b) 2% of the total power usage in ECBC+ Buildings c) 1% oftotal power usage in SuperECBC Buildings Record of design calculation for the losses shall be maintained. Load calculation shall be calculated up to the panel level:
7 · 2.7 Uninterruptible Power Supply (UPS) In all buildings, UPS shall meet or exceed the energy efficiency requirements listed in Table 7-4. Any Standards and Labeling program by BEE shall take precedence over requirements listed in this section:
90 · 2%
91 · 9%
93 · 8%
7 · 2.8 Renewable Energy Systems AlI buildings shall have provisions for installation of renewable energy systems in the future on rooftops or the site:
7 · 2.8.1 Renewable Energy Generating Zone (REGZ) a) A dedicated REGZ equivalent to at least 25 % of roof area or area required for generation of energy equivalent to 1% of total peak demand or connected load of the building, whichever is less, shall be provided in all buildings: b) The REGZ shall be free of any obstructions within its boundaries and from shadows cast by objects adjacent to the zone c) ECBC+ and SuperECBC building shall fulfil the additional requirements listed in Table 7-5 and Table 7-6 respectively:
7 · 2.8.2 Main Electrical Service Panel
7 · 2.8.3 Demarcation on Documents
8 · Definitions, Abbreviations, and Acronyms 8.1 General
8 · 2 Definitions
2 · ]
8 · 3 SI to IP Conversion Factors SI Unit
1 · cmh 1 Pa 1m 1m Imm 1 I/s 1 m2 1 W/m2 1 W/ lin m 1 Wlm4.K 1 W/ I-s-1 1 m2.K/W 1 "C 1 kWr
1 · kW
1 · kW
8 · 4 Abbreviations and Acronyms AFUE Annual fuel utilization efficiency AHRI Air-conditioning, Heating and Refrigeration Institute ANSI American National Standards Institute ARI Air-Conditioning and Refrigeration Institute ASHRAE American Society of Heating, Refrigerating and Air-Conditioning Engineers ASTM American Society for Testing and Materials BIS Bureau of Indian Standards Btu British thermal unit Btu/h British thermal units per hour Btu/h-ft2 ?F British thermal units per hour per square foot per degree Fahrenheit BUA Built up area Celsius cmh cubic meter per hour cm centimeter COP coefficient of performance DEF daylight extent factor EER energy efficiency ratio EPI energy performance index F Fahrenheit foot h hour h-ft2_?F/Btu hour per square foot per degree Fahrenheit per British thermal unit h-m2_%c/w hour per square meter per degree Celsius per Watt hp horsepower HVAC heating, ventilation, and air conditioning I-P inch-pound in. inch IPLV integrated part-load value IS Indian Standard ISO International Organization for Standardization kVA kilovolt-ampere
9 · Whole Building Performance Method
9 · 1 General
9 · 1.1 Scope The Whole Building Performance Method is an alternative to the Prescriptive Method compliance path contained in 54 through 57 of this Code. It applies to all building types covered by the Code as mentioned in 62.5.
9 · 1.2 Compliance building complies with the Code using the Whole Building Performance (WBP) Method, when the estimated EPI Ratio is equal to or less than 1,even though it may not comply with the specific provisions of the prescriptive requirements in 64 trough 57. The mandatory requirements of 54 through 87 (54.2, 85.2 , 86.2,and 87.2) shall be met when using the WBP Method:
9 · 1.3 Annual Energy Use Annual energy use for the purposes of the WBP Method shall be calculated in kilowatt-hours (kWh) of electricity use per year per unit area. Energy sources other than electricity that are used in the building shall be converted to kWh of electric energy at the rate of 0.75 kWh per megajoule: Note: The annual energy use calculation as per the Whole Building Performance Method is not a prediction of the actual energy use of the building once it gets operational. Actual energy performance of a building depends on a number of factors like weather, occupant behaviour, equipment performance and maintenance, among others, which are not covered by this Code:
9 · 1.4 Trade-offs Limited to Building Permit The WBP Method may be used for building permit applications that include less than the whole building; however, any design parameters that are not part of the building permit application shall be identical for both the Proposed Design and the Standard Design. Future improvements to the building shall comply with both the mandatory and prescriptive requirements of concurrent code:
9 · 1.5 Documentation Requirements Compliance shall be documented and compliance forms shall be submitted to the authority having jurisdiction: The information submitted shall include, at a minimum, the following: a) Summary describing the results of the analysis, including the annual energy use for the Proposed Design and the Standard Design, and software used: b) Brief description of the project with location, number of stories, space types, conditioned and unconditioned areas, hours of operation
9 · 2 Mandatory Requirements All requirements of 54.2, 55.2, 86.2,and 87.2 shall be met: These sections contain the mandatory provisions of the Code and are prerequisites for demonstrating compliance using the WBP Method:
9 · 3 Simulation Requirements
9 · 3.1 Energy Simulation Program The simulation software shall be a computer-based program for the analysis of energy consumption in buildings and be approved by the authority having jurisdiction. The simulation program shall, at a minimum, have the ability to model the following:
9 · 3.2 Climate Data
9 · 3.3 Compliance Calculations The Proposed Design and Standard Design shall be calculated using the following:
9 · 4 Calculating Energy Consumption of Proposed Design and Standard Design
9 · 4.1 Energy Simulation Model The simulation model for calculating the Proposed Design and the Standard Design shall be developed in accordance with the requirements in Table 9-1. The Standard Design is based on the mandatory and prescriptive requirements of the ECBC compliant building: The Standard Design will be the same for all compliance levels (ECBC, ECBC+, Super ECBC).
9 · 4.2 HVAC Systems The HVAC system type and related performance parameters for the Standard Design shall be determined from Table 9-2 and the following rules: a) Other components: Components and parameters not listed in Table 9-2 or otherwise specifically addressed in this subsection shall be identical to those inthe Proposed Design. Exception to $ 9.4.2(a): Where there are specific requirements in 85.2.2,the component efficiency in the Standard Design shall be adjusted to the lowest efficiency level allowed by the requirement for that component type: b) AIl HVAC and service water heating equipment in the Standard Design shall be modeled at the minimum efficiency levels, both part load and full load, in accordance with 55.2.2.
4 · Building Envelope
5 · Lighting
13 · Buildings of the listed occupancy types or spaces in Mixed-use Buildings with the listed occupancy types.
9 · 4.2.1 Minimum Outdoor air rates:
9 · 4.2.2 Fan Schedules
9 · 4.2.3 Fan Power
9 · 4.2.4 Design Airflow Rates
9 · 4.2.5 Economizers (airside and waterside) Airside economizers shall be modeled in the Standard Design as per the requirements of 55.3.3. Exception to 59.4.2.5: Airside economizer shall not be modeled for Standard Design HVAC System Type A
9 · 4.2.6 Energy Recovery Energy recovery shall be modeled in the Standard Design as per the requirements of 55.3.
9 · 4.2.7 Chilled Water Design Supply Temperatures Chilled water design supply temperature shall be modeled at 6.78 C and return temperature at 13.38 C
9 · 4.2.8 Chillers
9 · 4.2.9 Chilled Water Pumps Chilled and condenser water pumps for the Standard Design shall be modeled as per power and efficiency limits specified in Table 5-15. Standard Design chilled water pumps shall be modeled as primary-secondary with variable secondary flow.
9 · 4.2.10 Cooling Tower Standard Design cooling tower shall be modeled as an open circuit axial flow tower with power and efficiency as per Table 5-18. The fans shall be modeled as two speed: Condenser water design supply temperature shall be 29.4'C or 5.6*C approach to wet bulb temperature, whichever is lower, with a design temperature rise of 5.68C.
9 · 4.2.11 Boiler
9 · 4.2.12 Hot Water Design Supply Temperatures Hot water design supply temperature shall be modeled at 82*C and return temperature at 54'C.
9 · 4.2.13 Hot Water Pumps The Standard Design hot water pumps shall be modeled with a minimum efficiency of 70% and a pump power of 300 W/l-s-1.
9 · 4.2.14 Campus/ District Cooling Systems All district cooling plants shall be assumed to be on grid electricity, unless otherwise specified and supported through pertinent documents: New district plants shall comply with the mandatory requirements of ECBC irrespective of who owns and/or operates the district plant: Projects may choose either option A or option B given below for modelling campus/district cooling systems:
1 · ton hour = 0.85 kWh
1 · MBtu 1,000,000 Btu = 293 kWh
9 · 4.3 Compliance Thresholds for ECBC compliant, ECBC+ and SuperECBC Buildings For buildings to qualify as ECBCt and SuperECBC Buildings, the WBP Method shall be followed for the Standard Design as detailed above. The Proposed Design for ECBC+ and SuperECBC Buildings shall meet the mandatory provisions of 54.2, 55.2, 56.2, and 57.2. The EPI Ratio for ECBC+ and SuperECBC Buildings shall be equal to or less than the EPI Ratios listed under the applicable climate zone in Table 9-5 through Table 9-9 of 59.5.
9 · 5 Maximum Allowed EPI Ratios
0 · 91
0 · 81
0 · 88
0 · 76
0 · 85
0 · 77
0 · 85
0 · 75
0 · 86
0 · 77
0 · 86
0 · 78
0 · 88
0 · 76
0 · 77
0 · 66
0 · 85
0 · 76
0 · 86
0 · 74
0 · 81
0 · 70
0 · 82
0 · 68
9 · 6 Schedules
23 · 00-24.00 0.00
0 · 90
0 · 05
0 · 90
0 · 00
0 · 20
0 · 05
0 · 55
18 · 00-19.00 0.50 19.00-20.00 0.20 20.00-21.00 0.20 21.00-22.00 0.20 22.00-23.00 0.10 23.00-24.00 0.10
0 · 95 0.40 0.40 0.40 0.10
0 · 50 0.30 0.30 0.30 0.00
0 · 50 0.40 0.20 0.20 0.00 0.00
0 · 80 0.80 0.80 0.80 0.80 0.80
1 · 00 1.00 1.00 1.00 1.00 0.00
0 · 80 0.80 0.80 0.80 0.80 0.80
0 · 10
0 · 00
03 · 00-04.00 04.00-05.00 05.00-06.00 06.00-07:00 07:00-08.00 08.00-09:00 09.00-10.00 10.00-11:00 11.00-12.00 12.00-13.00
0 · 00 0.00 0.00 0.00 0.70 0.90
0 · 00 0.00 0.00 0.00 0.00
0 · 00 0.00 0.00 0.00 0.90
0 · 00
0 · 00 0.00 0.00 0.00 0.35
0 · 00 0.00 0.00 0.00 0.35 0.95 0.95 0.95 0.95 0.95
0 · 00 0.00 0.20 0.70
0 · 90
0 · 90
0 · 90
0 · 95
0 · 90
0 · 90
0 · 90 0.90
0 · 90
0 · 95
0 · 90
0 · 90
0 · 90
0 · 95
0 · 20
0 · 90
0 · 20
0 · 90
0 · 20
0 · 90
0 · 90
0 · 90
0 · 90
0 · 95
13 · 00-14.00 14.00-15.00 15.00-16.00 16.00-17.00 17.00-18.00 18.00-19.00 19.00-20.00 20.00-21.00 21.00-22.00 22.00-23.00
0 · 90 0.00 0.00 0.00 0.00
0 · 20 0.90 0.90 0.90 0.50
0 · 90 0.00 0.00 0.00 0.00
0 · 30 0.90 0.90 0.90 0.30
0 · 95 0.00 0.00 0.00 0.00
0 · 40 0.95 0.95 0.95 0.25
0 · 00
0 · 00
0 · 00
0 · 10
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
23 · 00-24.00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 70
0 · 00
0 · 90
0 · 70
0 · 35
0 · 35
08 · 00-09.00 09.00-10.00 10.00-11.00 11.00-12.00 12.00-13.00 13.00-14.00 14.00-15.00 15.00-16.00 16.00-17:00
0 · 90 0.90 0.90 0.20
0 · 90 0.90 0.90 0.90
0 · 90 0.90 0.90 0.20
0 · 90 0.90 0.90 0.90 0.90
0 · 95 0.95 0.95 0.20
0 · 95 0.95 0.95 0.95 0.95
0 · 90
0 · 90
0 · 90
0 · 95
0 · 90
0 · 20
0 · 90
0 · 30
0 · 95
0 · 40
0 · 00
0 · 90
0 · 00
0 · 90
0 · 00
0 · 95 0.95 0.95
0 · 00
0 · 90
0 · 00
0 · 90
0 · 00
0 · 00
0 · 90
0 · 00
0 · 90
0 · 00
17 · 00-18.00 18.00-19.00 19.00-20.00 20.00-21.00 21.00-22.00 22.00-23.00 23.00-24.00
0 · 00 0.00
0 · 50 0.00 0.00 0.00 0.00 0.00
0 · 00
0 · 30 0.10 0.00 0.00 0.00 0.00
0 · 00 0.00 0.00 0.00 0.00 0.00
0 · 25 0.00 0.00 0.00 0.00 0.00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
21 · 00-22.00 22.00-23.00 23.00-24.00
0 · 90 0.90 0.90
0 · 00 0.00 0.00
0 · 10 0.00 0.00
0 · 70 0.50 0.50
0 · 30 0.30 0.10
0 · 90 0.70 0.10
0 · 50 0.50 0.50
0 · 20 0.10 0.05
7 · days/ week
0 · 20 0.20 0.20 0.20 0.20
0 · 20 0.20 0.50 0.75 1.00 1.00 1.00
0 · 75
1 · 00
1 · 00 1.00 1.00 1.00 0.50 0.50 0.50 0.30 0.20 0.20
01 · 00-02.00 02.00-03.00 03.00-04.00 04.00-05.00 05.00-06.00 06.00-07:00 07:00-08.00 08.00-09.00 09.00-10.00 10.00-11.00
0 · 05 0.05 0.05 0.05 0.05 0.05 0.50
0 · 20 0.20 0.20 0.20 0.20
0 · 00 0.00 0.00 0.00 0.00
0 · 00
0 · 00
0 · 00 0.00 0.00 0.00 0.00 0.00 0.00 1.00 1.00 1.00
0 · 00
0 · 00 0.00 0.00 0.00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 20
0 · 00 1.00 1.00 1.00
0 · 75
0 · 00
0 · 20
0 · 60
1 · 00 1.00
0 · 00
0 · 30 0.30
0 · 60
0 · 80
0 · 30 0.25 0.25 0.25 0.25 0.25 0.10
0 · 80
1 · 00 1.00 1.00 1.00 1.00
1 · 00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
0 · 70 0.80 0.80 0.70 0.70
1 · 00 1.00 1.00 1.00 1.00
0 · 50
0 · 01
0 · 20
0 · 01
0 · 20
0 · 01
0 · 20
0 · 01 0.01 0.01
0 · 10 0.01 0.01
1 · 00 0.00 0.00
1 · 00 0.00 0.00
3 · 8 1 8 92 1 8 3 2 00.00-01:00 0.65 0.90 0.10 0.10 0.00 01.00-02:00 0.65 0.90 0.10 0.10 0.00 02.00-03.00 0.65 0.90 0.10 0.10 0.00 03.00-04.00 0.65 0.90 0.10 0.10 0.00 04.00-05.00 0.65 0.90 0.10 0.10 0.00 05.00-06.00 0.65 0.90 0.10 0.10 0.20 06.00-07:00 0.50 0.70 0.20 0.20 0.40 07:00-08.00 0.50 0.70 0.30 0.40 0.40 08.00-09.00 0.30 0.50 0.40 0.70 0.40 09.00-10.00 0.15 0.30 0.40 0.70 0.40 10.00-11.00 0.15 0.20 0.40 0.70 0.40 11.00-12.00 0.15 0.20 0.40 0.70 0.20 12.00-13.00 0.15 0.20 0.40 0.70 0.20 13.00-14.00 0.15 0.20 0.20 0.20 0.20 14.00-15.00 0.15 0.20 0.20 0.20 0.20 15.00-16.00 0.15 0.20 0.20 0.20 0.40 16.00-17.00 0.15 0.20 0.20 0.20 0.40 17.00-18.00 0.30 0.30 0.40 0.40 0.40 18.00-19.00 0.50 0.50 0.40 0.40 0.40 19.00-20.00 0.50 0.70 0.40 0.40 0.40 20.00-21.00 0.65 0.70 0.30 0.30 0.00 21.00-22.00 0.65 0.90 0.20 0.20 0.00 22.00-23.00 0.65 0.90 0.10 0.10 0.00 23.00-24.00 0.65 0.90 0.10 0.10 0.00
1 · 3 3 2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.50 0.00 0.70 0.30 0.70 0.50 0.70 0.50 0.70 0.50 0.70 0.50 0.30 0.00 0.30 0.00 0.30 0.50 0.30 0.50 0.70 0.00 0.70 0.30 0.70 0.30 0.70 0.00 0.70 0.30
1 · 8 0.00 0.00 0.00 0.00 0.00 0.00 0.50 0.80 0.80 0.80 0.80 0.00 0.00 0.50 0.80 0.80 0.30 0.30 0.00 0.50 0.90 0.90 0.90 0.90
0 · 00
0 · 50
0 · 00
0 · 50
0 · 00
0 · 50
0 · 00
0 · 50
33 · 1 27 J ! 28 { Time Period 3 3 1 8 80 80 3 2 1 8 3 3 1 8 2 8 N N N 00.00-01.00 0.05 0.05 0.50 0.30 0.20 0.20 0.05 0.05 0.30 01.00-02.00 0.05 0.05 0.05 0.20 0.20 0.20 0.05 0.05 0.10 02.00-03.00 0.05 0.05 0.05 0.20 0.20 0.20 0.05 0.05 0.10 03.00-04.00 0.05 0.05 0.05 0.20 0.20 0.20 0.05 0.05 0.10 04.00-05.00 0.05 0.05 0.05 0.20 0.20 0.20 0.05 0.05 0.10 05.00-06.00 0.05 0.05 0.05 0.30 0.20 0.20 0.05 0.05 0.10 06.00-07:00 0.10 0.10 0.10 0.50 0.30 0.30 0.05 0.05 0.30 07:00-08.00 0.30 0.30 0.30 0.50 0.40 0.60 0.10 0.10 0.30 08.00-09:00 0.90 0.60 0.90 0.50 0.70 0.90 0.30 0.30 0.30 09.00-10.00 0.90 0.60 0.90 0.50 0.20 0.20 0.95 0.70 0.30 10.00-11.00 0.90 0.60 0.90 0.35 0.20 0.20 0.95 0.70 0.30 11.00-12.00 0.90 0.60 0.90 0.35 0.20 0.20 0.95 0.70 0.30 12.00-13.00 0.90 0.60 0.90 0.35 0.20 0.20 0.95 0.70 0.30 13.00-14.00 0.50 0.50 0.50 0.35 0.20 0.20 0.50 0.70 0.30 14.00-15.00 0.90 0.60 0.90 0.35 0.20 0.20 0.95 0.70 0.30 15.00-16.00 0.90 0.60 0.90 0.35 0.20 0.20 0.95 0.70 0.30 16.00-17:00 0.90 0.60 0.90 0.35 0.20 0.20 0.95 0.70 0.30 17.00-18.00 0.95 0.60 0.95 0.35 0.30 0.30 0.95 0.70 0.30 18.00-19.00 0.50 0.50 0.95 0.70 0.50 0.50 0.30 0.30 0.30 19.00-20.00 0.30 0.30 0.95 0.90 0.50 0.50 0.10 0.10 0.30 20.00-21.00 0.0 0.0 0.95 0.90 0.50 0.70 0.10 0.10 0.30 21.00-22.00 0.20 0.20 0.95 0.90 0.70 0.70 0.10 0.10 0.30 22.00-23.00 0.10 0.10 0.95 0.70 0.40 0.40 0.05 0.05 0.30 23.00-24.00 0.05 0.05 0.95 0.40 0.20 0.20 0.05 0.05 0.30
00 · 00-01.00 01.00-02:00 02.00-03.00 03.00-04.00 04.00-05.00 05.00-06.00 06.00-07:00 07:00-08.00 08.00-09:00 09.00-10.00
0 · 10 0.10 0.10 0.10 0.10 0.20
0 · 10 0.10 0.10 0.10
1 · 1 0 ; 0 0.10 0 0 0.20 0 0 0.40 0.50 0 ; 0 0.50 0.60 1 0 0.50 0.60 1 1 1 0.35 0.40 1 1 10.00-11.00 0.15 0.20 1 11.00-12.00 0.15 0.20 1 13.00-14,0 0.15 0.20 1 14.00-15.00 0.15 0.20 15.00-16.00 0.15 0.20 16.00-17:00 0.35 0.40 H 13.00-19.00 050 0.60 1 19.00-20.00 0.50 0.60 20.00-21.00 0.50 0.60 21.00-22.00 0.30 0.40 22.00-23.00 0.20 0.30 23.00-24.00 0.10 0.10 1 1 0
7 · Days/ week
0 · 50
0 · 50
0 · 50
0 · 50 0.50 0.50 0.50
0 · 50
0 · 50
0 · 50
0 · 50
06 · 00-07:00 07:00-08.00 08.00-09.00 09.00-10.00 10.00-11.00 11.00-12.00 12.00-13.00 13.00-14.00 14.00-15.00
0 · 00 0.00 0.00 0.00 0.00 0.00
0 · 50 0.50 0.30 0.15 0.15 0.15
0 · 70 0.70
0 · 00 0.00 1.00
0 · 50 0.50 1.00 1.00 1.00 1.00 1.00 1.00 1.00
0 · 50 0.50 1.00 1.00 1.00 1.00
0 · 50 0.30 0.20 0.20
1 · 00
1 · 00
1 · 00
0 · 00
0 · 15
0 · 20
1 · 00
1 · 00
0 · 00
0 · 15
0 · 20
1 · 00
1 · 00
0 · 00
0 · 15
0 · 20
1 · 00
1 · 00
15 · 00-16.00 16.00-17.00 17.00-18.00 18.00-19.00 19.00-20.00 20.00-21.00 21.00-22.00 22.00-23.00 23.00-24.00
0 · 00 0.00 0.00 1.00 1.00 1.00 1.00 1.00 1.00
0 · 15 0.15 0.30 0.50 0.50 0.65 0.65
0 · 20 0.20 0.30 0.50 0.70 0.70
1 · 00 0.00 0.00 0.00 0.00 0.00
1 · 00 1.00 1.00 1.00 1.00 1.00
1 · 00 1.00 1.00 1.00 1.00 1.00
0 · 90
0 · 00
0 · 50
0 · 50
0 · 01
0 · 01
0 · 00
0 · 50
0 · 50
0 · 01
0 · 01
0 · 00
0 · 50
0 · 50
0 · 00
0 · 00
02 · 00-03.00 03.00-04.00 04.00-05.00 05.00-06.00 06.00-07:00 07:00-08.00 08.00-09.00 09.00-10.00 10.00-11.00 11.00-12.00 12.00-13.00
0 · 00 0.00
0 · 00
0 · 00 0.00 0.00 0.00 0.00
0 · 00 0.00 0.00 0.00 0.00 0.00
0 · 00 0.00 0.00 0.00 0.00
0 · 00
0 · 05 0.05 0.05 0.05 0.05
0 · 05 0.05 0.05 0.05 0.05 0.05 0.05
0 · 05 0.05 0.05 0.05 0.05 0.05 0.05
0 · 00
0 · 00
0 · 00 0.00 0.00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 05
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 05
0 · 20
0 · 20
0 · 20
0 · 20
0 · 20
0 · 20
0 · 20
0 · 20
0 · 20
0 · 40
0 · 40 0.60 0.70
0 · 40
0 · 40
0 · 20 0.30
0 · 20
0 · 50
0 · 50
0 · 40 0.60 0.60
0 · 60
0 · 60 0.60
0 · 60
0 · 50
0 · 95 0.95
0 · 50
0 · 60
0 · 70
0 · 50
0 · 70
0 · 50
13 · 00-14.00 14.00-15.00 15.00-16.00 16.00-17:00 17.00-18.00 18.00-19.00 19.00-20.00 20.00-21.00 21.00-22.00
0 · 60 0.70 0.70 0.70 0.70 0.90 0.90 0.90
0 · 90 0.90 0.90 0.90 0.90 0.95 0.95 0.95 0.00
0 · 60 0.70 0.70
0 · 90 0.90 0.90 0.90 0.90
0 · 50 0.50 0.50
0 · 70 0.70 0.80
0 · 95 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.05
0 · 50 0.50 0.50 0.70 0.95 0.95 0.95 0.95
0 · 60 0.60 0.40
0 · 70
0 · 50
0 · 80
0 · 40 0.40 0.80 0.80 0.80 0.80
0 · 70
0 · 50 0.60 0.60 0.60 0.60
0 · 80
0 · 90 0.90 0.90
0 · 95
0 · 95 0.95 0.95 0.95
0 · 95 0.95 0.40
0 · 00
0 · 40
0 · 50
22 · 00-23.00 23.00-24.00
0 · 00 0.00
0 · 00 0.00
0 · 30 0.10
0 · 30 0.10
0 · 60 0.30
0 · 95 0.95
0 · 05 0.05
0 · 30 0.30
0 · 80 0.80
0 · 05
0 · 05
0 · 05
0 · 05
0 · 05
0 · 05 0.05 0.05 0.90
0 · 05 0.50 0.50 0.90 0.90 0.90 0.90 0.90 0.90 0.90
0 · 10 0.10
0 · 10
0 · 10
0 · 20 0.40
0 · 20 0.40
0 · 90
0 · 70
0 · 70 0.80 0.95 0.95 0.95 0.95
0 · 90
0 · 70
0 · 90 0.90 0.90 0.90
0 · 70 0.70 0.70 0.70
17 · 00-18.00 18.00-19.00 19.00-20.00 20.00-21.00 21.00-22.00 22.00-23.00 23.00-24.00
0 · 90 0.90 0.90 0.50 0.05
0 · 90 0.90 0.90 0.90 0.90
0 · 80 0.80 0.80 0.80 0.80
0 · 95 0.95 0.95 0.95 0.80 0.60
0 · 05
0 · 90
0 · 50
0 · 05
0 · 90
0 · 30
0 · 40
7 · Days/ week
7 · Days/ week
1 · 00
1 · 00 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 1.00
0 · 00 0.00 0.00
0 · 50
0 · 00
0 · 50
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
0 · 00
1 · 00
0 · 00 0.00 0.00
1 · 00 1.00 1.00
1 · 00 1.00 1.00
0 · 00
1 · 00
1 · 00
0 · 00
1 · 00
1 · 00
0 · 00 o.00 1.00 1.00 1.00 1.00 1.00 1.00
1 · 00
1 · 00 100 1.00 1.00 1.00 1.00 1.00 1.00
100 · 1.00 1.00 1.00 1.00 1.00 1.00
02 · 00-03.00 03.00-04.00 04.00-05.00 05.00-06.00 06.00-07:00 07:00-08.00 08.00-09:00 09.00-10.00 10.00-11.00 11.00-12.00 12.00-13.00
0 · 00 0.00 0.00 0.00 0.00 0.00 0.00 0.20 0.40 0.60 0.60
0 · 00
0 · 05 0.05
0 · 05 0.05 0.05 0.05 0.05
0 · 00 0.00
0 · 00 0.00 0.00 0.00 0.00
0 · 00
0 · 00
0 · 05
0 · 00
0 · 00
0 · 05
0 · 00 0.00 0.10 0.10 0.20 0.40 0.70 0.70
0 · 00
0 · 05
0 · 00
0 · 05
0 · 05
0 · 10
0 · 00
0 · 05
0 · 05
0 · 10
0 · 20
0 · 20
0 · 05
0 · 20
0 · 40
0 · 50
0 · 90
0 · 40
0 · 60
0 · 95
0 · 90
0 · 70
0 · 70
0 · 95
0 · 90
0 · 80
13 · 00-14.00 14.00-15.00 15.00-16.00 16.00-17:00 17.00-18.00 18.00-19.00 19.00-20.00 20.00-21.00 21.00-22.00
0 · 60 0.70 0.70
0 · 90 0.90 0.90 0.90 0.90
0 · 95 0.95 0.95
0 · 90 0.90 0.90 0.90 0.90 0.90 0.90
0 · 70 0.70 0.70 0.70 0.80 0.80 0.80 0.80 0.00
0 · 95 0.95 0.95
0 · 70
0 · 95
0 · 95
0 · 70 0.90
0 · 95
0 · 95 0.95 0.95 0.95 0.00
0 · 95
0 · 95 0.95 0.95
0 · 90
0 · 95 0.95 0.00
0 · 90
0 · 50
0 · 00
0 · 05
0 · 05
22 · 00-23.00 23.00-24.00
0 · 00 0.00
0 · 00 0.00
0 · 05 0.05
0 · 05 0.05
0 · 00 0.00
0 · 00 0.00
03 · 00-04.00 04.00-05.00 05.00-06.00 06.00-07:00 07:00-08.00 08.00-09.00 09.00-10.00 10.00-11.00 11.00-12.00 12.00-13.00 13.00-14.00
0 · 20 0.20 0.20 0.00 0.00
0 · 00 0.00
0 · 05 0.05 0.05 0.05 0.05
0 · 00
0 · 0 0 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1 0.00 o.o0 1.00 1.00 1.00 1.00 0.20 0 0.20
0 · 00
0 · 00
0 · 00
0 · 05
1 · 00
1 · 00
1 · 00
1 · 00
1 · 00
1 · 00
1 · 00
1 · 00
1 · 00
1 · 00
14 · 00-15.00 15.00-16.00 16,00-13,00 18.00-19.00 19.00-20.00 20.00-21.00 21.00-22.00 22.00-23.00 23.00-24.00
1 · 00 1.00 100 1.00 1.00 1.00 0.20 0.00 0.00
1 · 00 1.00 100 1.00 1.00 1.00 0.50 0.05 0.05
0 · 00 0.20 0.20 0.20 0.80 0.80 0.80 0.80 0.80
0 · 00 0.40 0.75 0.95 0.95 0.95 0.95 0.95 0.95
0 · 00 0.30 0.50 0.95 0.95
0 · 00 0.20 0.50 0.50 0.50
0 · 00 0.00 0.00 0.00 0.00
0 · 00 1.00 1.00 1.00 1.00
0 · 10
0 · 80 0.80 0.80 0.80 0.80 0.80 0.80 0.80
0 · 95
0 · 50
0 · 00
1 · 00
0 · 95
0 · 50
0 · 00
1 · 00
0 · 95
0 · 50
0 · 00
1 · 00
0 · 95
0 · 50
0 · 00
1 · 00
16 · 00-17.00 17.00-18.00 18.00-19.00 19.00-20.00 20.00-21.00 21.00-22.00 22.00-23.00 23.00-24.00
0 · 80 0.80 0.50 0.20 0.20
0 · 95 0.95 0.95 0.40 0.40 0.40 0.10 0.10
0 · 95 0.95 0.50 0.30 0.30 0.30 0.00 0.00
0 · 50 0.50 0.50 0.40
0 · 00 0.00 0.80 0.80 0.80 0.80 0.80 0.80
1 · 00 1.00 1.00 1.00 1.00 1.00 1.00 0.00
0 · 80 0.80 0.80 0.80 0.80 0.80 0.80 0.80
0 · 20 0.20 0.00 0.00
0 · 20
0 · 10 0.10
10 · Appendix A: Default Values for Typical Constructions 10.1 Procedure for Determining Fenestration Product U-factor and Solar Heat Gain Coefficient
5 · 4.2.1.1 and 5 4.2.1.2 require that U-factors and solar heat gain coefficients (SHGC) be determined for the overall fenestration product (including the sash and frame) in accordance with ISO 15099. The building envelope trade-off option in $ 4.3.5 requires the use of visible light transmittance (VLT):
10 · 2 Default U-factors and Solar Heat Gain Coefficients for Unrated Fenestration Products All fenestration with U-factors, SHGC, or visible light transmittance determined, certified, and labeled in accordance ISO 15099 shall be assigned those values.
10 · 2.1 Unrated Vertical Fenestration: Unlabeled vertical fenestration, both operable and fixed, shall be assigned the U-factors, SHGCs, and visible light transmittances in Table 10.2.1.
7 · 1
3 · 4
5 · 1
10 · 2.2 Unrated Sloped Glazing and Skylights Unrated sloped glazing and skylights, both operable and fixed, shall be assigned the SHGCs and visible light transmittances in Table 10-1. To determine the default U-factor for unrated sloped
1 · 0.3 Typical Roof Constructions
1 · 0.4 Typical Wall Constructions
2 · Thermo-Physical-Optical Property Database of Construction Materials, U.S.- India Joint Center for Building Energy Research and Development (CBERD) and Ministry of New and Renewable Energy (MNRE): 3 This is not an all-inclusive list: The database of thermal properties of building materials is available at BEE website (https:/ /www.beeindia gov.in/):
1 · 9654
1 · 3957
0 · 4751
1 · 4107
0 · 7013
1750 · 2390 2262 1000 571
1 · 012 1.5094 3.084 0.6134 0.2527
2 · 0921 1.9427 1.583 3.8165 1.423
0 · 0321
0 · 0374
0 · 2252
1 · 693
2049 · 954 581 529 49 3535 3473 2650 96 623 588 542
1 · 2729 0.2654 0.1588 0.2062 0.0351 2.4351 2.5433 2.372 0.045 0.2527 0.202 0.1033
1 · 2887 1.1423 0.5359 0.5769 0.0339 2.2511 2.1996 2.5275 0.1089 0.6033 1.1918 0.626
2911 · 2630 3006
2 · 3636 2.7752 2.7447
2 · 2349 2.1869 2.0954
1 · 9617 2.0732 1.2621
0 · 1286 0.6051 2.8108 0.2045
0 · 7078 1.2809 2.1943 0.961
0 · 2459 44.117 0.071 0.2739 0.2652
0 · 6509 4.1896 0.3222 0.6427 1.3389
1 · 7248 1.4763 0.271
1 · 3413 1.2737 0.974
0 · 1353
0 · 9526
0 · 221 0.0364
0 · 7258 0.0685
0 · 5027 0.0372
1 · 6968 0.0704
0 · 4994 1.5331 0.9907
1 · 2167 1.6259 0.4382
3 · 7603 5.6405
1 · 8277 2.777
0 · 0766
0 · 0384 0.0461 0.0561 0.1679 0.2886 0.3075 3.0097 2.1363
0 · 0763 0.0904 0.1486 0.5034 1.0258 1.1343 1.5957 2.4484
274 · 353
0 · 0943 0.0983
0 · 2753 0.2621
7950 · 241 760 665 2500 2500 3197
13 · 5633 0.2331 0.2237 0.2369 1.0493 1.0428 2.921
3 · 6351 0.5512 0.7098 0.8412 1.9227 1.8904 2.2184
1191 · 788
0 · 2977 0.2363
0 · 8245 0.7075
2719 · 1520
1 · 4786 0.6314
1 · 8049 0.9951
802 · 3126
0 · 2652 3.4258
0 · 8715 2.2852
11 · Appendix B: Climate Zone Map of Uttar Pradesh
12 · Appendix C: Air-Side Economizer Acceptance Procedures
12 · 1 Construction Inspection Prior to Performance Testing, verify and document the following: (a) System controls are wired correctly to ensure economizer is fully integrated (i.e. economizer will operate when mechanical cooling is enabled): (b) Economizer lockout control sensor location is adequate (open to air but not exposed to direct sunlight nor in an enclosure; away from sources of building exhaust; at least 8 meters away from cooling towers). (c) System is provided with barometric relief, relief fan or return fan to control building pressure:
12 · 2 Equipment Testing
13 · Appendix D: Compliance Forms Envelope Summary Uttar Pradesh Energy Conservation Building Code 2018 Compliance Forms Project Info Project Address Date For Building Department Use
2 · 2 z Mandatory Provisions Section 4.2) 4.2.1 Fenestration rating
4 · 2.1.1
4 · 2.1.2
4 · 2.2
4 · 2.3
4 · 2.4
4 · 2.6
4 · 3.1
4 · 3.2
4 · 3.2
4 · 3.3.1
5 · 2.2
5 · 2.3
5 · 2.3.1
5 · 2.3.2
5 · 2.2.3
5 · 2.2.4
5 · 2.2.5
5 · 2.4
5 · 2.4.1
5 · 2.4.2
5 · 2.4.3
5 · 2.5
5 · 2.5.1
5 · 2.6
5 · 2.6.1
5 · 2.6.2
5 · 2.7
5 · 2.8
5 · 2.9
5 · 2.9.1
5 · 2.9.2
5 · 2.9.3
5 · 2.9.4
5 · 2.9.5
5 · 2.9.6
5 · 3.1
5 · 3.2
5 · 3.3
5 · 3.4
5 · 3.4
5 · 3.4.3
5 · 3.4.4
5 · 3.9
5 · 3.5
5 · 3.5.1
5 · 3.5.2
5 · 3.5.3
5 · 3.5.4
5 · 4
5 · 5
2 · z
6 · 2.1.1
6 · 2.1.6
6 · 2.3
2 · z
7 · 21.1
7 · 21.2
7 · 2.1.3
7 · 22.2
7 · 2.3
7 · 22.4
7 · 2.5
7 · 2.6
7 · 2.7
7 · 2.8
7 · 2.8.1
7 · 2.8.2
7 · 2.8.3
8 · 2 7
4 · 2
5 · 2
6 · 2
7 · 2
9 · 3
9 · 4
14 · Appendix E: BEE approved list of software to show compliance'
Uttar Pradesh Shasan Atrikt Urja Shrot Vibhag — THE ENERGY CONSERVATION ACT, 2001 — Roop's Law Assist Statutes